3Ph in / 3Ph out Online UPS,isolation transformer offer full isolation
Support N+X parallel redundancy and Maintenance bypass
EPO/ECO/SNMP/USB/RS232 optional.
True double-conversion
DSP technology guarantees high performance
Output power factor 0.9
Always striving toward excellence, SOROTEC has developed to be a market-driven and customer-oriented enterprise. We focus on strengthening the capabilities of scientific research and completing service businesses. We have set up a customer service department to better provide customers with prompt services including order tracking notice. online low frequency ups Today, SOROTEC ranks the top as a professional and experienced supplier in the industry. We can design, develop, manufacture, and sell different series of products on our own combining the efforts and wisdom of all our staff. Also, we are responsible for offering a wide range of services for customers including technical support and prompt Q&A services. You may discover more about our new product online low frequency ups and our company by directly contacting us.Materials of online low frequency ups is actually quite .
Key Features:
1.True double-conversion
2.DSP technology guarantees high performance
3.Output power factor 0.9
4.Wide input voltage range (110-300 VAC)
5.Active power factor correction in all phases
6.50Hz/60Hz frequency converter mode
7.ECO mode operation for energy saving
8.Accepts dual-mains inputs
9.Emergency power off function (EPO)
10.Generator compatible
11.SNMP+USB+RS-232 multiple communications
12.3-stage extendable charging design for optimized battery performance
13.Adjustable battery numbers
14.Maintenance bypass available
15.Optional N+X parallel redundancy
16.Optional isolation transformer offers full isolation and complete common mode noise rejection
MODEL | HP9335C Plus 10-30KVA | ||||||||
10K | 10K-XL | 15K | 15K-XL | 20K | 20K-XL | 30K | 30K-XL | ||
CAPACITY | 10KVA / 9KW | 15KVA / 13.5KW | 20KVA / 18KW | 30KVA / 27KW | |||||
PHASE | 3 Phase with Neutral | ||||||||
INPUT | |||||||||
Voltage Range | Low Line Loss | 110 VAC(Ph-N) ± 3 % at 50% Load ; 176 VAC(Ph-N) ± 3 % at 100% Load | |||||||
Low Line Comeback | Low Line Loss Voltage + 10V | ||||||||
High Line Loss | 300 VAC(Ph-N) ± 3 % | ||||||||
High Line Comeback | High Line Loss Voltage - 10V | ||||||||
Phase | Three phase with ground | ||||||||
Power Factor | ≥ 0.99 at 100% Load | ||||||||
OUTPUT | |||||||||
Output voltage | 208/220/230/240VAC(Ph-N) | ||||||||
AC Voltage Regulation | ± 1% | ||||||||
Frequency Range (Synchronized Range) | 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system | ||||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||||||
Overload | AC mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | |||||||
Battery mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | ||||||||
Current Crest Ratio | 3:1 max | ||||||||
Harmonic Distortion | ≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load | ||||||||
Transfer Time | Line←→Battery | 0 ms | |||||||
Inverte←→Bypass | 0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass) | ||||||||
Line←→ECO | <10 ms | ||||||||
EFFICIENCY | |||||||||
AC mode | > 89% | > 89% | > 89% | > 90% | |||||
Battery Mode | > 86% | > 88% | > 87% | > 89% | |||||
BATTERY | |||||||||
Standard Model | Type | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | ||||
Numbers | 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 3 x 20(18-20 adjustable) | |||||
Recharge Time | 9 hours recover to 90% capacity | ||||||||
Charging Current | 1.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
Long-run Model | Type | Depending on applications | |||||||
Numbers | 18-20 | ||||||||
Charging Current | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 12.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
PHYSICAL | |||||||||
Standard Model | Dimension,DxWxH(mm) | 832 X250X894 | 832 X250X1275 | ||||||
Long-run Model | Dimension,DxWxH(mm) | 609 X250X768 | 832 X250X828 | ||||||
ENVIRONMENT | |||||||||
Operation Temperature | 0 ~ 40°C (the battery life will down when > 25°C) | ||||||||
Operation Humidity | <95 % and non-condensing | ||||||||
Operation Altitude | <1000m | ||||||||
Acoustic Noise Level | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter | |||||||
MANAGEMENT | |||||||||
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC | ||||||||